3.2.2 Warnings
In case of a warning, the protection relay continues to operate except for those protection
functions possibly affected by the fault, and the green Normal LED remains lit as during
normal operation.
Warnings are indicated with the text Warning additionally provided with the name of the
warning, a numeric code and the date and time on the LHMI. The warning indication
message can be manually cleared.
If a warning appears, record the name and code so that it can be provided
to ABB customer service.
Table 24: Warning indications and codes
Warning indication Warning code Additional information
Warning
Watchdog reset
10 A watchdog reset has occurred.
Warning
Power down det.
11 The auxiliary supply voltage has dropped
too low.
Warning
IEC61850 error
20 Error when building the IEC 61850 data
model.
Warning
Modbus error
21 Error in the Modbus communication.
Warning
DNP3 error
22 Error in the DNP3 communication.
Warning
Dataset error
24 Error in the Data set(s).
Warning
Report cont. error
25 Error in the Report control block(s).
Warning
GOOSE contr. error
26 Error in the GOOSE control block(s).
Warning
SCL config error
27 Error in the SCL configuration file or the file
is missing.
Warning
Logic error
28 Too many connections in the
configuration.
Warning
SMT logic error
29 Error in the SMT connections.
Warning
GOOSE input error
30 Error in the GOOSE connections.
ACT error 31 Error in the ACT connections.
Warning
GOOSE Rx. error
32 Error in the GOOSE message receiving.
Table continues on next page
1MAC059074-MB A Section 3
Basic functions
615 series ANSI 73
Technical Manual