8.1.6.2 Function block
A070778-ANSI V1 EN
Figure 471: Function block
8.1.6.3 Signals
Table 808: IG Input signals
Name Type Default Description
IG SIGNAL 0 Ground current
BLOCK BOOLEAN 0=False Block signal for all binary outputs
Table 809: IG Output signals
Name Type Description
HIGH_ALARM BOOLEAN High alarm
HIGH_WARN BOOLEAN High warning
8.1.6.4 Settings
Table 810: IG Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
A Hi high limit res 0.00...40.00 xIn 1 0.20 High alarm current limit
A high limit res 0.00...40.00 xIn 1 0.05 High warning current limit
A deadband res 100...100000 1 2500 Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Table 811: IG Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Measurement mode 1=RMS
2=DFT
2=DFT Selects used measurement mode
Section 8 1MAC059074-MB A
Measurement functions
914 615 series ANSI
Technical Manual