Parameter Values (Range) Unit Step Default Description
Operation mode 0=Pulsed
1=Toggle
-1=Off
-1=Off Operation mode for generic control point
Pulse length 10...3600000 ms 10 1000 Pulse length for pulsed operation mode
Description SPCGAPC1
Output 15
Generic control point description
Operation mode 0=Pulsed
1=Toggle
-1=Off
-1=Off Operation mode for generic control point
Pulse length 10...3600000 ms 10 1000 Pulse length for pulsed operation mode
Description SPCGAPC1
Output 16
Generic control point description
3.17.12 Generic up-down counter CTR
3.17.12.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Generic up-down counter UDFCNT UDCNT CTR
3.17.12.2 Function block
GUID-222CC574-D72D-4426-876C-526D7C264C1E V1 EN
Figure 99: Function block
3.17.12.3 Functionality
The multipurpose generic up-down counter function CTR counts up or down for each
positive edge of the corresponding inputs. The counter value output can be reset to zero or
preset to some other value if required.
The function provides up-count and down-count status outputs, which specify the relation
of the counter value to a loaded preset value and to zero respectively.