3.15.4.2 Functionality
The GOOSERCV_INT8 function is used to connect the GOOSE 8 bit integer inputs to the
application.
3.15.4.3 Signals
Table 72: GOOSERCV_INT8 Output signals
Name Type Description
OUT INT8 Output signal
VALID BOOLEAN Output signal
3.15.5 GOOSERCV_INTL function block
3.15.5.1 Function block
GUID-241A36E0-1BB9-4323-989F-39668A7B1DAC V1 EN
Figure 50: Function block
3.15.5.2 Functionality
The GOOSERCV_INTL function is used to connect the GOOSE double binary input to
the application and extracting single binary position signals from the double binary
position signal.
The OP output signal indicates that the position is open. Default value (0) is used if
VALID output indicates invalid status.
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate state.
The default value (0) is used if VALID output indicates invalid status.