Pickup value Add and Pickup value settings. This allows a temporal increase or decrease
of the level detector depending on the sign and value of the Pickup value Add setting, for
example, when the emergency start is activated. If, for example, Pickup value is 100,
Pickup value Add is 20 and the ENA_ADD input is active, the input signal needs to rise
above 120 before MAP trips.
4.11.6 Signals
Table 661: MAP Input signals
Name Type Default Description
AI_VALUE FLOAT32 0.0 Analogue input value
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
ENA_ADD BOOLEAN 0=False Enable pickup added
Table 662: MAP Output signals
Name Type Description
TRIP BOOLEAN Trip
PICKUP BOOLEAN Pickup
4.11.7 Settings
Table 663: MAP Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Pickup value -10000.0...10000.0 0.1 0.0 Pickup value
Pickup value Add -100.0...100.0 0.1 0.0 Pickup value Add
Trip delay time 0...200000 ms 100 0 Trip delay time
Table 664: MAP Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Operation mode 1=Over
2=Under
1=Over Operation mode
Table 665: MAP Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 100 0 Reset delay time
Absolute hysteresis 0.01...100.00 0.01 0.10 Absolute hysteresis for operation
1MAC059074-MB A Section 4