EasyManua.ls Logo

ABB 615 Series - Settings

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Default Description
BLOCK BOOLEAN 0=False Block signal for all binary outputs
REM_FLT_ARC BOOLEAN 0=False Remote Fault arc detected
OPR_MODE BOOLEAN 0=False Operation mode input
Table 645: AFD Output signals
Name Type Description
TRIP BOOLEAN Trip
ARC_FLT_DET BOOLEAN Fault arc detected=light signal output
4.9.7 Settings
Table 646: AFD Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Phase pickup value 0.50...40.00 xIn 0.01 2.50 Operating phase current
Ground pickup value 0.05...8.00 xIn 0.01 0.20 Operating residual current
Operation mode 1=Light+current
2=Light only
3=BI controlled
1=Light+current Operation mode
Table 647: AFD Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
4.9.8 Monitored data
Table 648: AFD Monitored data
Name
Type Values (Range) Unit Description
AFD Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Section 4 1MAC059074-MB A
Protection functions
748 615 series ANSI
Technical Manual

Table of Contents

Other manuals for ABB 615 Series

Related product manuals