3.3.2 Functionality
The protection relay includes a global conditioning function LEDPTRC that is used with
the protection indication LEDs.
LED indication control should never be used for tripping purposes. There
is a separate trip logic function 86/94 available in the relay configuration.
LED indication control is preconfigured in a such way that all the protection function
general pickup and trip signals are combined with this function (available as output
signals OUT_START and OUT_OPERATE). These signals are always internally
connected to Pickup and Trip LEDs. LEDPTRC collects and combines phase information
from different protection functions (available as output signals OUT_ST_A /_B /_C
and OUT_OPR_A /_B /_C). There is also combined ground fault information collected
from all the ground-fault functions available in the relay configuration (available as output
signals OUT_ST_NEUT and OUT_OPR_NEUT).
3.4 Programmable LEDs
3.4.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
identification
Programmable LEDs LED LED LED
3.4.2 Function block
GUID-00339108-34E4-496C-9142-5DC69F55EE7A V1 EN
Figure 11: Function block
3.4.3 Functionality
The programmable LEDs reside on the right side of the display on the LHMI.
1MAC059074-MB A Section 3
Basic functions
615 series ANSI 75
Technical Manual