3.16.4 T_HEALTH function block
3.16.4.1 Function block
GUID-B5FCAE66-8026-4D5F-AC38-028E5A8171BB V1 EN
Figure 57: Function block
3.16.4.2 Functionality
The T_HEALTH function evaluates enumerated data of “Health” data attribute. This
function block can only be used with GOOSE.
The IN input can be connected to GOOSERCV_ENUM function block, which is
receiving the LD0.LLN0.Health.stVal data attribute sent by another device.
The outputs OK, WARNING and ALARM are extracted from the enumerated input value.
Only one of the outputs can be active at a time. In case the GOOSERCV_ENUM function
block does not receive the value from the sending device or it is invalid, the default value
(0) is used and the ALARM is activated in the T_HEALTH function block.
3.16.4.3 Signals
Table 83: T_HEALTH Input signals
Name
Type Default Description
IN1 Any 0 Input signal
Table 84: T_HEALTH Output signals
Name
Type Description
OK BOOLEAN Output signal
WARNING BOOLEAN Output signal
ALARM BOOLEAN Output signal
Section 3 1MAC059074-MB A
Basic functions
144 615 series ANSI
Technical Manual