Table 428: 87L Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 0 Reset delay time
Minimum trip time 45...60000 ms 1 45 Minimum trip time for stabilized stage IDMT
curves
4.3.1.9 Monitored Data
Table 429: 87L Monitored data
Name Type Values (Range) Unit Description
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
I_AMPL_LOC_A FLOAT32 0.00...40.00 xIr Local phase A amplitude after
correction
I_AMPL_LOC_B FLOAT32 0.00...40.00 xIr Local phase B amplitude after
correction
I_AMPL_LOC_C FLOAT32 0.00...40.00 xIr Local phase C amplitude after
correction
I_AMPL_REM_A FLOAT32 0.00...40.00 xIr Remote phase A amplitude
after correction
I_AMPL_REM_B FLOAT32 0.00...40.00 xIr Remote phase B amplitude
after correction
I_AMPL_REM_C FLOAT32 0.00...40.00 xIr Remote phase C amplitude
after correction
ID_A FLOAT32 0.00...80.00 xIr Differential current phase A
ID_B FLOAT32 0.00...80.00 xIr Differential current phase B
ID_C FLOAT32 0.00...80.00 xIr Differential current phase C
IB_A FLOAT32 0.00...80.00 xIr Stabilization current phase A
IB_B FLOAT32 0.00...80.00 xIr Stabilization current phase B
IB_C FLOAT32 0.00...80.00 xIr Stabilization current phase C
I_ANGL_DIFF_A FLOAT32 -180.00...180.00 deg Current phase angle
differential between local and
remote, phase A
I_ANGL_DIFF_B
FLOAT32 -180.00...180.00 deg Current phase angle
differential between local and
remote, phase B
I_ANGL_DIFF_C
FLOAT32 -180.00...180.00 deg Current phase angle
differential between local and
remote, phase C
87L
Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
IA-diff FLOAT32 0.00...80.00 Differential current phase A
Table continues on next page
Section 4 1MAC059074-MB A
Protection functions
498 615 series ANSI
Technical Manual