3.14.4.5 Settings
Table 68: RESTVTR Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Primary voltage 0.100...440.000 kV 0.001 11.547 Primary voltage
Secondary voltage 60...210 V 1 100 Secondary voltage
Amplitude corr. 0.9000...1.1000 0.0001 1.0000 Amplitude correction
Angle correction -20.0000...20.0000 deg 0.0001 0.0000 Angle correction factor
3.14.4.6 Monitored data
Monitored data is available in three locations.
Monitoring/I/O status/Analog inputs
Monitoring/IED status/SMV traffic
Monitoring/IED status/SMV accuracy
3.15 GOOSE function blocks
GOOSE function blocks are used for connecting incoming GOOSE data to application.
They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32 data types.
Common signals
The VALID output indicates the validity of received GOOSE data, which means in case
of valid, that the GOOSE communication is working and received data quality bits (if
configured) indicate good process data. Invalid status is caused either by bad data quality
bits or GOOSE communication failure. See IEC 61850 engineering guide for details.
The OUT output passes the received GOOSE value for the application. Default value (0)
is used if VALID output indicates invalid status. The IN input is defined in the GOOSE
configuration and can always be seen in SMT sheet.
Settings
The GOOSE function blocks do not have any parameters available in LHMI or PCM600.
1MAC059074-MB A Section 3
Basic functions
615 series ANSI 135
Technical Manual