Table 889: 29GS Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Event delay 0...60000 ms 1 30000 Event delay of the intermediate position
Vendor 0 External equipment vendor
Serial number 0 External equipment serial number
Model 0 External equipment model
9.2.8 Monitored data
Table 890: 52-TOC,29DS Monitored data
Name Type Values (Range) Unit Description
POSITION Dbpos 0=intermediate
1=open
2=closed
3=faulty
Apparatus position indication
Table 891: 29GS Monitored data
Name Type Values (Range) Unit Description
POSITION Dbpos 0=intermediate
1=open
2=closed
3=faulty
Apparatus position indication
9.2.9 Technical revision history
Table 892: 52-TOC, 29DS Technical revision history
Technical revision
Change
B Maximum and default values changed to 60 s and 30
s respectively for
Event delay
settings.
C Outputs OPENPOS and CLOSEPOS are forced to
“FALSE” in case status is Faulty (11).
Table 893: 29GS Technical revision history
Technical revision
Change
B Maximum and default values changed to 60 s and 30
s respectively for
Event delay
settings.
C Outputs OPENPOS and CLOSEPOS are forced to
“FALSE” in case status is Faulty (11).
1MAC059074-MB A Section 9
Control functions
615 series ANSI 975
Technical Manual