10.1.7 Settings
Table 917: PQI Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Demand interval 0=1 minute
1=5 minutes
2=10 minutes
3=15 minutes
4=30 minutes
5=60 minutes
6=180 minutes
2=10 minutes Time interval for demand calculation
Demand window 1=Sliding
2=Non-sliding
1=Sliding Demand calculation window type
TDD alarm limit 1.0...100.0 % 0.1 50.0 TDD alarm limit
Table 918: PQI Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Initial Dmd current 0.10...1.00 xIn 0.01 1.00 Initial demand current
10.1.8 Monitored data
Table 919: PQI Monitored data
Name
Type Values (Range) Unit Description
Max demand TDD IA FLOAT32 0.00...500.00 % Maximum demand TDD for
phase A
Max demand TDD IB FLOAT32 0.00...500.00 % Maximum demand TDD for
phase B
Max demand TDD IC FLOAT32 0.00...500.00 % Maximum demand TDD for
phase C
Time max dmd TDD
IA
Timestamp Time of maximum demand
TDD phase A
Time max dmd TDD
IB
Timestamp Time of maximum demand
TDD phase B
Time max dmd TDD
IC
Timestamp Time of maximum demand
TDD phase C
3SMHTDD_A FLOAT32 0.00...500.00 % 3 second mean value of TDD
for phase A
DMD_TDD_A FLOAT32 0.00...500.00 % Demand value for TDD for
phase A
3SMHTDD_B FLOAT32 0.00...500.00 % 3 second mean value of TDD
for phase B
Table continues on next page
Section 10 1MAC059074-MB A
Power quality measurement functions
1036 615 series ANSI
Technical Manual