EasyManua.ls Logo

ABB 615 Series - Function Block; Functionality; Signals; T_BIN_TCMD Function Block

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 92: Conversion from integer to Boolean
IN RAISE LOWER
0 FALSE FALSE
1 FALSE TRUE
2 TRUE FALSE
x FALSE FALSE
3.16.8.3 Signals
Table 93: T_TCMD_BIN input signals
Name Type Default Description
IN INT32 0 Input signal
Table 94: T_TCMD_BIN output signals
Name Type Description
RAISE BOOLEAN Raise command
LOWER BOOLEAN Lower command
3.16.9 T_BIN_TCMD function block
3.16.9.1 Function block
GUID-54A013A3-E253-4A06-B033-01C7E11EC997 V1 EN
Figure 62: Function block
3.16.9.2 Functionality
The T_BIN_TCMD function is used to convert Boolean input signals to 32 bit integer
output signals.
Table 95: Conversion from Boolean to integer
RAISE
LOWER OUT
FALSE FALSE 0
FALSE TRUE 1
TRUE FALSE 2
Section 3 1MAC059074-MB A
Basic functions
148 615 series ANSI
Technical Manual

Table of Contents

Other manuals for ABB 615 Series

Related product manuals