To ensure that both the uploaded file types are generated from the same data content, the
files need to be uploaded successively. Once either of the files is uploaded, the recording
buffer is halted to give time to upload the other file.
Data content of the load profile record is sequentially updated. Therefore,
the size attribute for both COMTRADE files is "0".
192 . 168 . 10 . 187 L D P 1
0 A B B L D P 1 . C F G
0 A B B L D P 1 . D A T
GUID-43078009-323D-409C-B84A-5EB914CDEE53 V1 EN
Figure 101: Load profile record file naming
3.19.1.4 Clearing of record
The load profile record can be cleared with Reset load profile rec via HMI,
communication or the ACT input in PCM600. Clearing of the record is allowed only on
the engineer and administrator authorization levels.
The load profile record is automatically cleared if the quantity selection parameters are
changed or any other parameter which affects the content of the COMTRADE
configuration file is changed. Also, if data source for selected quantity is removed, for
example, with ACT, the load profile recorder stops recording and previously collected
data are cleared.
Section 3 1MAC059074-MB A
Basic functions
202 615 series ANSI
Technical Manual