Section 14 Technical data
Table 976: Dimensions
Description Value
Width Frame 6.97 inches (177 mm)
Case 6.46 inches (164 mm)
Height Frame 6.97 inches (177 mm), 4U
Case 6.30 inches (160 mm)
Depth 7.92 inches (201 mm)
Weight Complete protection relay 9.0 lbs (4.1 kg)
Plug-in unit only 4.6 lbs (2.1 kg)
Table 977: Power supply
Description Type 1 Type 2
Nominal auxiliary voltage V
n
100, 110, 120, 220, 240 V AC, 50
and 60 Hz
24, 30, 48, 60 V DC
48, 60, 110, 125, 220, 250 V DC
Maximum interruption time in the
auxiliary DC voltage without
resetting the relay
50 ms at V
n
Auxiliary voltage variation 38...110% of V
n
(38...264 V AC) 50...120% of V
n
(12...72 V DC)
80...120% of V
n
(38.4...300 V DC)
Start-up threshold 19.2 V DC (24 V DC × 80%)
Burden of auxiliary voltage supply
under quiescent (P
q
)/operating
condition
DC <13.0 W (nominal)/<18.0 W
(max.)
AC <16.0 W (nominal)/<21.0 W
(max.)
DC <13.0 W (nominal)/<18.0 W
(max.)
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Fuse type T4A/250 V
1MAC059074-MB A Section 14
Technical data
615 series ANSI 1167
Technical Manual