A071274-ANSI V1 EN
Figure 523: Three shots with three initiation lines
If the sequence is initiated from the INIT_1 line, that is, the overcurrent protection high
stage, the sequence is one shot long. If the sequence is initiated from the INIT_2 or
INIT_3 lines, the sequence is two shots long.
Table 906: Settings for configuration example 2
Setting name Setting value
Shot number CBB1
1
Init signals CBB1
1 (line 1)
First reclose time
0.0s (an example)
Shot number CBB2
1
Init signals CBB2
6 (lines 2 and 3 = 2+4 = 6)
Second reclose time
0.2s (an example)
Shot number CBB3
2
Init signals CBB3
6 (lines 2 and 3 = 2+4 = 6)
Third reclose time
10.0s
9.4.6.4 Delayed initiation lines
The autoreclose function consists of six individual autoreclose initiation lines
INIT_1...INIT 6 and three delayed initiation lines:
•
DEL_INIT_2
•
DEL_INIT_3
•
DEL_INIT_4
DEL_INIT_2 and INIT_2 are connected together with an OR-gate, as are inputs 3 and
4. Inputs 1, 5 and 6 do not have any delayed input. From the autoreclosing point of view,
it does not matter whether INIT_x or DEL_INIT_x line is used for shot initiation or
blocking.
1MAC059074-MB A Section 9
Control functions
615 series ANSI 1023