4.4.2.7 Settings
Table 489: 46PD Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Pickup value 10...100 % 1 10 Pickup value
Trip delay time 100...30000 ms 1 100 Trip delay time
Table 490: 46PD Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Table 491: 46PD Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Min phase current 0.05...0.30 xIn 0.01 0.10 Minimum phase current
4.4.2.8 Monitored data
Table 492: 46PD Monitored data
Name
Type Values (Range) Unit Description
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
RATIO_I2_I1 FLOAT32 0.00...999.99 % Measured current ratio I2 / I1
46PD Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
4.4.2.9 Technical data
Table 493: 46PD Technical data
Characteristic
Value
Operation accuracy Depending on the frequency of the measured
current: f
n
±2 Hz
±2% of the set value
Pickup time <70 ms
Reset time Typically 40 ms