4.8.2.7 Settings
Table 632: 32R/32O Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Pickup value 0.01...2.00 xSn 0.01 1.00 Pickup value
Trip delay time 40...300000 ms 10 40 Trip delay time
Directional mode 2=Forward
3=Reverse
2=Forward Directional mode
Power angle -90...90 deg 1 0 Adjustable angle for power
Table 633: 32R/32O Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Measurement mode 1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
3=Pos Seq Selection of power calculation method
Table 634: 32R/32O Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
Pol reversal 0=False
1=True
0=False Reverse the definition of the power direction
4.8.2.8 Monitored data
Table 635: 32R/32O Monitored data
Name
Type Values (Range) Unit Description
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
P FLOAT32 -160.000...160.0
00
xSn Active power
Q FLOAT32 -160.000...160.0
00
xSn Reactive power
Table continues on next page
Section 4 1MAC059074-MB A
Protection functions
732 615 series ANSI
Technical Manual