output is set for a specific duration using the Pulse time setting. Both timers use the same
setting parameter.
GUID-9BE17BA5-70D3-442B-8D24-8544C7A9441A V1 EN
Figure 81: A = Trip pulse is shorter than Cold load time setting, B = Trip pulse is
longer than Cold load time setting
Signals
Table 149: 62TPM Input signals
Name Type Default Description
IN1 BOOLEAN 0=False Input 1
IN2 BOOLEAN 0=False Input 2
Table 150: 62TPM Output signals
Name
Type Description
OUT1 BOOLEAN Output 1 status
OUT2 BOOLEAN Output 2 status
Settings
Table 151: 62TPM Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Cold load time 0...300 min 1 0 Cold load time
3.17.3 Pulse timer function block 62PT
3.17.3.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse timer (8 pcs) PTGAPC PT 62PT
Section 3 1MAC059074-MB A
Basic functions
168 615 series ANSI
Technical Manual