Warning indication Warning code Additional information
Warning
AFL error
33 Analog channel configuration error.
Warning
SMV config error
34 Error in the SMV configuration.
Warning
Comm. channel down
35 Redundant Ethernet (HSR/PRP)
communication interrupted.
Warning
Unack card comp.
40 A new composition has not been
acknowledged/accepted.
Warning
Protection comm.
50 Error in protection communication.
Warning
ARC1 cont. light
85 A continuous light has been detected on
the ARC light input 1.
Warning
ARC2 cont. light
86 A continuous light has been detected on
the ARC light input 2.
Warning
ARC3 cont. light
87 A continuous light has been detected on
the ARC light input 3.
Warning
RTD card error,X130
96 Temporary error occurred in RTD card
located in slot X130.
Warning
RTD meas. error,X130
106 Measurement error in RTD card located in
slot X130.
For further information on warning indications, see the operation manual.
3.3 LED indication control
3.3.1 Function block
GUID-B5D22C6D-951D-4F34-BE68-F5AF08580140 V2 EN
Figure 10: Function block
Section 3 1MAC059074-MB A
Basic functions
74 615 series ANSI
Technical Manual