Table 302: 37 Output signals
Name Type Description
TRIP BOOLEAN Trip
TRIP_A BOOLEAN Trip phase A
TRIP_B BOOLEAN Trip phase B
TRIP_C BOOLEAN Trip phase C
PICKUP BOOLEAN Pickup
PICKUP_A BOOLEAN Pickup phase A
PICKUP_B BOOLEAN Pickup phase B
PICKUP_C BOOLEAN Pickup phase C
4.1.8.7 Settings
Table 303: 37 Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Current block value 0.00...0.50 xIn 0.01 0.10 Low current setting to block internally
Pickup value 0.01...1.00 xIn 0.01 0.50 Current setting to pickup
Trip delay time 50...200000 ms 10 2000 Trip delay time
Table 304: 37 Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Operation mode 1=Three Phase
2=Single Phase
1=Three Phase Number of phases needed to pickup
Table 305: 37 Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Section 4 1MAC059074-MB A
Protection functions
296 615 series ANSI
Technical Manual