EasyManua.ls Logo

ABB 615 Series - Phase Selection Logic

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The operation of 21FL can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
BLOCK
TRIGG_XC0F
Phase
selection
logic
Fault
impedance
and
distance
calculation
TRIGG
ALARM
Trigger
detection
Alarm
indication
I_A
I_B
I_C
V_A_AB
V_B_BC
V_C_CA
I
0
I
1
I
2
V
0
V
1
V
2
Recorded
data
GUID-5DEC6352-438F-4B66-88F1-F72C0138AECF V1 EN
Figure 410: Functional module diagram
5.7.4.1 Phase selection logic
Identification of the faulty phases is provided by the built-in Phase Selection Logic based
on combined impedance and current criterion. Phase selection logic is virtually setting-
free and has only one parameter, Z Max phase load, for discriminating a large symmetrical
load from a three-phase fault. The setting Z Max phase load can be calculated using the
equation.
Z Max phase load = 0 8
2
.
max
V
S
xy
GUID-BDFF7D0D-9323-4610-84C6-A9B4234136B3 V1 EN (Equation 137)
V
xy
Nominal phase-to-phase voltage
S
max
Maximum three-phase load
For example, if V
xy
= 20 kV and S
max
= 1 MVA, then Z Max phase load = 320.0 Ω.
The identification of the faulty phases is compulsory for the correct operation of 21FL.
This is because only one of the impedance-measuring elements (fault loops) provides the
correct result for a specific fault type. A three-phase fault is an exception and theoretically
1MAC059074-MB A Section 5
Protection related functions
615 series ANSI 805
Technical Manual

Table of Contents

Other manuals for ABB 615 Series

Related product manuals