Table 868: 29GS Output signals
Name Type Description
SELECTED BOOLEAN Object selected
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
OKPOS BOOLEAN Apparatus position is ok
OPEN_ENAD BOOLEAN Opening is enabled based on the input status
CLOSE_ENAD BOOLEAN Closing is enabled based on the input status
9.1.7 Settings
Table 869: 52 Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation mode disable / disable
Select timeout 10000...300000 ms 10000 30000 Select timeout in ms
Pulse length 10...60000 ms 1 200 Open and close pulse length
Control model 0=status-only
1=direct-with-
normal-security
4=sbo-with-
enhanced-security
4=sbo-with-
enhanced-security
Select control model
Operation timeout 10...60000 ms 1 500 Timeout for negative termination
Identification CBXCBR1 switch
position
Control Object identification
Table 870: 52 Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Operation counter 0...10000 1 0 Breaker operation cycles
Adaptive pulse 0=False
1=True
1=True Stop in right position
Event delay 0...10000 ms 1 200 Event delay of the intermediate position
Vendor 0 External equipment vendor
Serial number 0 External equipment serial number
Model 0 External equipment model
Section 9 1MAC059074-MB A
Control functions
968 615 series ANSI
Technical Manual