Table 139: RS Output signals
Name Type Description
Q BOOLEAN Q status
NOTQ BOOLEAN NOTQ status
Technical revision history
Table 140: RS Technical revision history
Technical revision Change
L The name of the function has been changed from SR
to RS.
3.17.2 Minimum pulse timer
3.17.2.1 Minimum pulse timer 62TP
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Minimum pulse timer (2 pcs) TPGAPC TP 62TP
Function block
62TP
OUT2
OUT1
IN1
IN2
GUID-637103D5-5868-4D09-9229-F4FD68423519 V1 EN
Figure 76: Function block
Functionality
The Minimum pulse timer function TP contains two independent timers. The function has
a settable pulse length (in milliseconds). The timers are used for setting the minimum
pulse length for example, the signal outputs. Once the input is activated, the output is set
for a specific duration using the Pulse time setting. Both timers use the same setting
parameter.