9.3.9 Technical data
Table 901: 25 Technical data
Characteristic
Value
Operation accuracy Depending on the frequency of the voltage
measured: f
n
±1 Hz
Voltage:
±3.0% of the set value or ±0.01 × V
n
Frequency:
±10 mHz
Phase angle:
±3°
Reset time
<50 ms
Reset ratio Typically 0.96
Trip time accuracy in definite time mode ±1.0% of the set value or ±20 ms
9.3.10 Technical revision history
Table 902: 25 Technical revision history
Technical revision Change
B Internal improvement
C Added new setting
Voltage source switch
to switch
the input signals V_BUS (bus voltage) and V_LINE
(line voltage) between each other.