Table 899: 25 Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Control mode 1=Continuous
2=Command
1=Continuous Selection of synchro check command or
Continuous control mode
Close pulse 200...60000 ms 10 200 Breaker closing pulse duration
Phase shift -180...180 deg 1 0 Correction of phase difference between
measured U_BUS and U_LINE
Minimum Syn time 0...60000 ms 10 0 Minimum time to accept synchronizing
Maximum Syn time 100...6000000 ms 10 2000 Maximum time to accept synchronizing
Energizing time 100...60000 ms 10 100 Time delay for energizing check
Closing time of CB 40...250 ms 10 60 Closing time of the breaker
Voltage source switch 0=False
1=True
0=False Voltage source switch
9.3.8 Monitored data
Table 900: 25 Monitored data
Name Type Values (Range) Unit Description
ENERG_STATE Enum 0=Unknown
1=Both Live
2=Live L, Dead B
3=Dead L, Live B
4=Both Dead
Energization state of Line and
Bus
U_DIFF_MEAS FLOAT32 0.00...1.00 xUn Calculated voltage amplitude
difference
FR_DIFF_MEAS FLOAT32 0.000...0.100 xFn Calculated voltage frequency
difference
PH_DIFF_MEAS FLOAT32 0.00...180.00 deg Calculated voltage phase
angle difference
U_DIFF_SYNC BOOLEAN 0=False
1=True
Voltage difference out of limit
for synchronizing
PH_DIF_SYNC BOOLEAN 0=False
1=True
Phase angle difference out of
limit for synchronizing
FR_DIFF_SYNC BOOLEAN 0=False
1=True
Frequency difference out of
limit for synchronizing
25 Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status