3.15.5.3 Signals
Table 73: GOOSERCV_INTL Output signals
Name
Type Description
POS_OP BOOLEAN Position open output signal
POS_CL BOOLEAN Position closed output signal
POS_OK BOOLEAN Position OK output signal
VALID BOOLEAN Output signal
3.15.6 GOOSERCV_CMV function block
3.15.6.1 Function block
GUID-4C3F3A1A-F5D1-42E1-840F-6106C58CB380 V1 EN
Figure 51: Function block
3.15.6.2 Functionality
The GOOSERCV_CMV function is used to connect GOOSE measured value inputs to the
application. The MAG_IN (amplitude) and ANG_IN (angle) inputs are defined in the
GOOSE configuration (PCM600).
The MAG output passes the received GOOSE (amplitude) value for the application.
Default value (0) is used if VALID output indicates invalid status.
The ANG output passes the received GOOSE (angle) value for the application. Default
value (0) is used if VALID output indicates invalid status.
3.15.6.3 Signals
Table 74: GOOSERCV_CMV Output signals
Name
Type Description
MAG FLOAT32 Output signal (amplitude)
ANG FLOAT32 Output signal (angle)
VALID BOOLEAN Output signal
1MAC059074-MB A Section 3
Basic functions
615 series ANSI 139
Technical Manual