9.4.9 Monitored data
Table 912: 79 Monitored data
Name
Type Values (Range) Unit Description
DISA_COUNT BOOLEAN 0=False
1=True
Signal for counter disabling
FRQ_OPR_CNT INT32 0...2147483647 Frequent operation counter
FRQ_OPR_AL BOOLEAN 0=False
1=True
Frequent operation counter
alarm
STATUS Enum -1=Bad
1=Ready
2=InProgress
3=Successful
4=WaitingForTri
p
5=TripFromProte
ction
6=FaultDisappe
ared
7=WaitToCompl
ete
8=CBclosed
9=CycleUnsucce
ssful
10=Unsuccessfu
l
11=Aborted
AR status signal for IEC61850
INPRO_1 BOOLEAN 0=False
1=True
Reclosing shot in progress,
shot 1
INPRO_2 BOOLEAN 0=False
1=True
Reclosing shot in progress,
shot 2
INPRO_3 BOOLEAN 0=False
1=True
Reclosing shot in progress,
shot 3
INPRO_4 BOOLEAN 0=False
1=True
Reclosing shot in progress,
shot 4
INPRO_5 BOOLEAN 0=False
1=True
Reclosing shot in progress,
shot 5
DISCR_INPRO BOOLEAN 0=False
1=True
Signal indicating that
discrimination time is in
progress
CUTOUT_INPRO
BOOLEAN 0=False
1=True
Signal indicating that cut-out
time is in progress
SUC_RECL BOOLEAN 0=False
1=True
Indicates a successful
reclosing sequence
UNSUC_CB BOOLEAN 0=False
1=True
Indicates an unsuccessful CB
closing
CNT_SHOT1 INT32 0...2147483647 Resetable operation counter,
shot 1
Table continues on next page
Section 9 1MAC059074-MB A
Control functions
1030 615 series ANSI
Technical Manual