Example 1
The protection operation time is 0.5 seconds, the Fourth delay in SOTF parameter is set
to "1" and the Str 2 delay shot 4 parameter is 0.05 seconds. The protection pickup signal
is connected to the DEL_INIT_2 input.
If the protection picks up after the circuit breaker closes, the fast trip follows after the set
0.05 seconds. The total trip time is the protection pickup delay + 0.05 seconds + the time
it takes to open the circuit breaker.
9.4.7 Signals
Table 908: 79 Input signals
Name Type Default Description
INIT_1 BOOLEAN 0=False AR initialization / blocking signal 1
INIT_2 BOOLEAN 0=False AR initialization / blocking signal 2
INIT_3 BOOLEAN 0=False AR initialization / blocking signal 3
INIT_4 BOOLEAN 0=False AR initialization / blocking signal 4
INIT_5 BOOLEAN 0=False AR initialization / blocking signal 5
INIT_6 BOOLEAN 0=False AR initialization / blocking signal 6
DEL_INIT_2 BOOLEAN 0=False Delayed AR initialization / blocking signal 2
DEL_INIT_3 BOOLEAN 0=False Delayed AR initialization / blocking signal 3
DEL_INIT_4 BOOLEAN 0=False Delayed AR initialization / blocking signal 4
BLK_RECL_T BOOLEAN 0=False Blocks and resets reclose time
BLK_RCLM_T BOOLEAN 0=False Blocks and resets reclaim time
BLK_THERM BOOLEAN 0=False Blocks and holds the reclose shot from the thermal
overload
CB_POS BOOLEAN 0=False Circuit breaker position input
CB_READY BOOLEAN 1=True Circuit breaker status signal
INC_SHOTP BOOLEAN 0=False A zone sequence coordination signal
INHIBIT_RECL BOOLEAN 0=False Interrupts and inhibits reclosing sequence
RECL_ON BOOLEAN 0=False Level sensitive signal for allowing (high) / not allowing
(low) reclosing
SYNC BOOLEAN 0=False Synchronizing check fulfilled