5.3 Master trip 86/94
5.3.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Master trip TRPPTRC Master Trip 86/94
5.3.2 Function block
A071286-ANSI V2 EN
Figure 394: Function block
5.3.3 Functionality
The master trip function 86/94 is intended to be used as a trip command collector and
handler after the protection functions. The features of this function influence the trip
signal behavior of the circuit breaker. The minimum trip pulse length can be set when the
non-latched mode is selected. It is also possible to select the latched or lockout mode for
the trip signal.
5.3.4 Operation principle
The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are “Enable” and “Disable”.
When the 86/94 function is disabled, all trip outputs which are intended to
go through the function to the circuit breaker trip coil are blocked.
The operation of 86/94 can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
Section 5 1MAC059074-MB A
Protection related functions
784 615 series ANSI
Technical Manual