Table 625: 32U Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Table 626: 32U Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Measurement mode 1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
3=Pos Seq Selection of power calculation method
Reset delay time 0...60000 ms 10 20 Reset delay time
Pol reversal 0=False
1=True
0=False Reverse the definition of the power direction
Disable time 0...60000 ms 1000 0 Additional wait time after CB closing
4.8.1.8 Monitored data
Table 627: 32U Monitored data
Name
Type Values (Range) Unit Description
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
P FLOAT32 -160.000...160.0
00
xSn Active power
Q FLOAT32 -160.000...160.0
00
xSn Reactive power
S FLOAT32 0.000...160.000 xSn Apparent power
PF_ANGLE FLOAT32 -180.00...180.00 deg Power factor angle
32U Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status