3.17.2.2 Minimum pulse timer 62TPS
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Minimum second pulse timer (2 pcs) TPSGAPC TPS 62TPS
Function block
62TPS
OUT2
OUT1
IN1
IN2
GUID-F47E9742-1C94-4E8E-B2D8-CC9F3A8FE0EF V1 EN
Figure 78: Function block
Functionality
The Minimum second pulse timer function 62TPS contains two independent timers. The
function has a settable pulse length (in seconds). The timers are used for setting the
minimum pulse length for example, the signal outputs. Once the input is activated, the
output is set for a specific duration using the Pulse time setting. Both timers use the same
setting parameter.
GUID-9BE17BA5-70D3-442B-8D24-8544C7A9441A V1 EN
Figure 79: A = Trip pulse is shorter than Cold load time setting, B = Trip pulse is
longer than Cold load time setting
Signals
Table 145: 62TPS Input signals
Name
Type Default Description
IN1 BOOLEAN 0=False Input 1
IN2 BOOLEAN 0=False Input 2
Section 3 1MAC059074-MB A
Basic functions
166 615 series ANSI
Technical Manual