8.1.12.2 Function block
GUID-C6D692B2-FEA1-4450-A108-09C229A9CC0C V2 EN
Figure 477: Function block
8.1.12.3 Signals
Table 843: SP,SE Input signals
Name Type Default Description
I_A SIGNAL 0 Phase A current
I_B SIGNAL 0 Phase B current
I_C SIGNAL 0 Phase C current
V_A SIGNAL 0 Phase A voltage
V_B SIGNAL 0 Phase B voltage
V_C SIGNAL 0 Phase C voltage
RSTACM BOOLEAN 0=False Reset of accumulated energy reading
8.1.12.4 Settings
Table 844: SP,SE Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Power unit Mult 3=k
6=M
3=k Unit multiplier for presentation of the power
related values
Energy unit Mult 3=k
6=M
3=k Unit multiplier for presentation of the energy
related values
Active power Dir 1=Forward
2=Reverse
1=Forward Direction of active power flow: forward, reverse
Reactive power Dir 1=Forward
2=Reverse
1=Forward Direction of reactive power flow: forward,
reverse
1MAC059074-MB A Section 8
Measurement functions
615 series ANSI 931
Technical Manual