3.17.4.2 Function block
62TOF
Q2
Q1
Q3
Q4
Q7
Q5
Q6
Q8
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
GUID-0F47E31C-225B-4B3B-91DD-7731EDD0AC9E V1 EN
Figure 84: Function block
3.17.4.3 Functionality
The time delay off (8 pcs) function 62TOF can be used, for example, for a drop-off-
delayed output related to the input signal. The function contains eight independent timers.
There is a settable delay in the timer. Once the input is activated, the output is set
immediately. When the input is cleared, the output stays on until the time set with the Off
delay time setting has elapsed.
t0 t1+dt t2 t3 t5+dt
dt = Off delay time
t1 t4 t5
GUID-D45492E6-5FBC-420C-B1BF-B3A1F65ADF96 V1 EN
Figure 85: Timer operation
3.17.4.4 Signals
Table 156: 62TOF Input signals
Name
Type Default Description
IN1 BOOLEAN 0=False Input 1 status
IN2 BOOLEAN 0=False Input 2 status
IN3 BOOLEAN 0=False Input 3 status
IN4 BOOLEAN 0=False Input 4 status
IN5 BOOLEAN 0=False Input 5 status
Table continues on next page
1MAC059074-MB A Section 3
Basic functions
615 series ANSI 171
Technical Manual