Table 453: 87C Input signals
Name Type Default Description
I_C SIGNAL 0 Phase C current
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
Table 454: 87A Output signals
Name Type Description
TRIP BOOLEAN Trip
PICKUP BOOLEAN Pickup
Table 455: 87B Output signals
Name Type Description
TRIP BOOLEAN Trip
PICKUP BOOLEAN Pickup
Table 456: 87C Output signals
Name
Type Description
TRIP BOOLEAN Trip
PICKUP BOOLEAN Pickup
4.3.4.8 Settings
Table 457: 87A Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Trip value 1.0...200.0 %In 1.0 5.0 Pickup value, percentage of the nominal
current
Minimum trip time 20...300000 ms 10 20 Minimum trip time
Table 458: 87A Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Table 459: 87A Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 565
Technical Manual