EasyManua.ls Logo

ABB 615 Series - Technical Data

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Values (Range) Unit Description
V2_DB FLOAT32 0.00...4.00 xUn Negative sequence voltage
amplitude, reported value
V2_RANGE Enum 0=normal
1=high
2=low
3=high-high
4=low-low
Negative sequence voltage
amplitude range
V1_INST FLOAT32 0.00...4.00 xUn Positive sequence voltage
amplitude, instantaneous
value
V1_ANGL
FLOAT32 -180.00...180.00 deg Positive sequence voltage
angle
V1_DB FLOAT32 0.00...4.00 xUn Positive sequence voltage
amplitude, reported value
V1_RANGE Enum 0=normal
1=high
2=low
3=high-high
4=low-low
Positive sequence voltage
amplitude range
V0_INST FLOAT32 0.00...4.00 xUn Zero sequence voltage
amplitude, instantaneous
value
V0_ANGL
FLOAT32 -180.00...180.00 deg Zero sequence voltage angle
V0_DB FLOAT32 0.00...4.00 xUn Zero sequence voltage
amplitude, reported value
V0_RANGE Enum 0=normal
1=high
2=low
3=high-high
4=low-low
Zero sequence voltage
amplitude range
8.1.10.6 Technical data
Table 836: V1, V2, V0 Technical data
Characteristic
Value
Operation accuracy Depending on the frequency of the voltage
measured: f
n
±2 Hz
At voltages in range 0.01…1.15 × V
n
±1.0% or ±0.002 × V
n
Suppression of harmonics DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
Section 8 1MAC059074-MB A