Name Type Values (Range) Unit Description
V2_DB FLOAT32 0.00...4.00 xUn Negative sequence voltage
amplitude, reported value
V2_RANGE Enum 0=normal
1=high
2=low
3=high-high
4=low-low
Negative sequence voltage
amplitude range
V1_INST FLOAT32 0.00...4.00 xUn Positive sequence voltage
amplitude, instantaneous
value
V1_ANGL
FLOAT32 -180.00...180.00 deg Positive sequence voltage
angle
V1_DB FLOAT32 0.00...4.00 xUn Positive sequence voltage
amplitude, reported value
V1_RANGE Enum 0=normal
1=high
2=low
3=high-high
4=low-low
Positive sequence voltage
amplitude range
V0_INST FLOAT32 0.00...4.00 xUn Zero sequence voltage
amplitude, instantaneous
value
V0_ANGL
FLOAT32 -180.00...180.00 deg Zero sequence voltage angle
V0_DB FLOAT32 0.00...4.00 xUn Zero sequence voltage
amplitude, reported value
V0_RANGE Enum 0=normal
1=high
2=low
3=high-high
4=low-low
Zero sequence voltage
amplitude range
8.1.10.6 Technical data
Table 836: V1, V2, V0 Technical data
Characteristic
Value
Operation accuracy Depending on the frequency of the voltage
measured: f
n
±2 Hz
At voltages in range 0.01…1.15 × V
n
±1.0% or ±0.002 × V
n
Suppression of harmonics DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
Section 8 1MAC059074-MB A
Measurement functions
926 615 series ANSI