Name Type Values (Range) Unit Description
CNT_SHOT2 INT32 0...2147483647 Resetable operation counter,
shot 2
CNT_SHOT3 INT32 0...2147483647 Resetable operation counter,
shot 3
CNT_SHOT4 INT32 0...2147483647 Resetable operation counter,
shot 4
CNT_SHOT5 INT32 0...2147483647 Resetable operation counter,
shot 5
COUNTER INT32 0...2147483647 Resetable operation counter,
all shots
SHOT_PTR INT32 1...7 Shot pointer value
MAN_CB_CL BOOLEAN 0=False
1=True
Indicates CB manual closing
during reclosing sequence
SOTF BOOLEAN 0=False
1=True
Switch-onto-fault
79 Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
9.4.10 Technical data
Table 913: 79 Technical data
Characteristic
Value
Trip time accuracy ±1.0% of the set value or ±20 ms
9.4.11 Technical revision history
Table 914: 79 Technical revision history
Technical revision
Change
B The PROT_DISA output removed and removed the
related settings
C The default value of the
CB closed Pos status
setting
changed from "True" to "False"
D SHOT_PTR output range 0...7 (earlier 0...6)
E Monitored data ACTIVE transferred to be ACT visible
output. SHOT_PTR output range 1...7.
F Internal improvement
1MAC059074-MB A Section 9
Control functions
615 series ANSI 1031
Technical Manual