3.14.1.2 Functionality
The SMVSENDER function block is used for activating the SMV sending functionality.
It adds/removes the sampled value control block and the related data set into/from the
sending device's configuration. It has no input or output signals.
SMVSENDER can be disabled with the Operation setting value “off”. If the
SMVSENDER is disabled from the LHMI, it can only be enabled from the LHMI. When
disabled, the sending of the samples values is disabled.
3.14.1.3 Settings
Table 61: SMVSENDER Settings
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation
3.14.2 IEC 61850-9-2 LE sampled values receiving SMVRECEIVER
3.14.2.1 Function block
UL1
SMVRECEIVER
UL2
UL3
Uo
GUID-EB0B6F8A-724A-4090-A94B-0BD935BB03F4 V1 EN
Figure 43: Function block
3.14.2.2 Functionality
The SMVRECEIVER function block is used for activating the SMV receiving
functionality.
3.14.2.3 Signals
Table 62: SMVRECEIVER Output signals
Name
Type Description
UL1 INT32-UL1 IEC61850-9-2 phase 1 voltage
UL2 INT32-UL2 IEC61850-9-2 phase 2 voltage
UL3 INT32-UL3 IEC61850-9-2 phase 3 voltage
U0 INT32-Uo IEC61850-9-2 residual voltage
Section 3 1MAC059074-MB A
Basic functions
130 615 series ANSI
Technical Manual