10.3.9 Monitored data
Table 933: PQSS Monitored data
Name
Type Values (Range) Unit Description
ST_A BOOLEAN 0=False
1=True
Pickup Phase A (Voltage
Variation Event in progress)
ST_B BOOLEAN 0=False
1=True
Pickup Phase B (Voltage
Variation Event in progress)
ST_C BOOLEAN 0=False
1=True
Pickup Phase C (Voltage
Variation Event in progress)
INSTSWELLCNT INT32 0...2147483647 Instantaneous swell operation
counter
MOMSWELLCNT INT32 0...2147483647 Momentary swell operation
counter
TEMPSWELLCNT INT32 0...2147483647 Temporary swell operation
counter
MAXDURSWELLCN
T
INT32 0...2147483647 Maximum duration swell
operation counter
INSTDIPCNT INT32 0...2147483647 Instantaneous dip operation
counter
MOMDIPCNT INT32 0...2147483647 Momentary dip operation
counter
TEMPDIPCNT INT32 0...2147483647 Temporary dip operation
counter
MAXDURDIPCNT INT32 0...2147483647 Maximum duration dip
operation counter
MOMINTCNT INT32 0...2147483647 Momentary interruption
operation counter
TEMPINTCNT INT32 0...2147483647 Temporary interruption
operation counter
SUSTINTCNT INT32 0...2147483647 Sustained interruption
operation counter
MAXDURINTCNT INT32 0...2147483647 Maximum duration
interruption operation counter
PQSS Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Time Timestamp Time
Table continues on next page
Section 10 1MAC059074-MB A
Power quality measurement functions
1058 615 series ANSI