Parameter Values (Range) Unit Step Default Description
VVa swell time 1 0.5...54.0 cycles 0.1 0.5 Voltage variation swell duration 1
Voltage swell set 2 100.0...140.0 % 0.1 120.0 Swell limit 2 in % of reference voltage
VVa swell time 2 10.0...80.0 cycles 0.1 10.0 Voltage variation swell duration 2
Voltage swell set 3 100.0...140.0 % 0.1 120.0 Swell limit 3 in % of reference voltage
VVa swell time 3 2000...60000 ms 10 2000 Voltage variation swell duration 3
Voltage Int set 0.0...100.0 % 0.1 10.0 Interruption limit in % of reference voltage
VVa Int time 1 0.5...30.0 cycles 0.1 3.0 Voltage variation Int duration 1
VVa Int time 2 10.0...180.0 cycles 0.1 30.0 Voltage variation Int duration 2
VVa Int time 3 2000...60000 ms 10 3000 Voltage variation interruption duration 3
VVa Dur Max 100...3600000 ms 100 60000 Maximum voltage variation duration
Table 931: PQSS Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Variation enable 1=Swell
2=Dip
3=Swell + dip
4=Interruption
5=Swell + Int
6=Dip + Int
7=Swell+dip+Int
7=Swell+dip+Int Enable variation type
Table 932: PQSS Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Phase supervision 1=Ph A
2=Ph B
3=Ph A + B
4=Ph C
5=Ph A + C
6=Ph B + C
7=Ph A + B + C
7=Ph A + B + C Monitored voltage phase
Phase mode 1=Three Phase
2=Single Phase
2=Single Phase Three/Single phase mode
1MAC059074-MB A Section 10
Power quality measurement functions
615 series ANSI 1057
Technical Manual