4.5.2.8 Settings
Table 525: 27 Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Pickup value 0.05...1.20 xUn 0.01 0.90 Pickup value
Time multiplier 0.05...15.00 0.01 1.00 Time multiplier in IEC/ANSI IDMT curves
Trip delay time 60...300000 ms 10 60 Trip delay time
Operating curve type 5=ANSI DT
15=IEC DT
21=Inv. Curve A
22=Inv. Curve B
23=Programmable
15=IEC DT Selection of time delay curve type
Table 526: 27 Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Type of reset curve 1=Immediate
2=Def time reset
1=Immediate Selection of reset curve type
Type of time reset 1=Freeze Op timer
2=Decrease Op
timer
1=Freeze Op timer Selection of time reset
Table 527: 27 Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Num of pickup phases 1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases required for trip activation
Curve parameter A 0.005...200.000 1 1.000 Parameter A for customer programmable
curve
Curve parameter B 0.50...100.00 1 1.00 Parameter B for customer programmable
curve
Curve parameter C 0.0...1.0 1 0.0 Parameter C for customer programmable
curve
Curve parameter D 0.000...60.000 1 0.000 Parameter D for customer programmable
curve
Curve parameter E 0.000...3.000 1 1.000 Parameter E for customer programmable
curve
Voltage selection 1=phase-to-earth
2=phase-to-phase
2=phase-to-phase Parameter to select phase or phase-to-phase
voltages
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 625