Parameter Values (Range) Unit Step Default Description
Ps Seq V deadband 100...100000 1 10000 Deadband configuration value for positive
sequence voltage for integral calculation.
(percentage of difference between min and
max as 0,001 % s)
Ng Seq V Hi high Lim
0.00...4.00 xUn 1 0.20 High alarm voltage limit for negative sequence
voltage
Ng Seq V High limit 0.00...4.00 xUn 1 0.05 High warning voltage limit for negative
sequence voltage
Ng Seq V low limit 0.00...4.00 xUn 1 0.00 Low warning voltage limit for negative
sequence voltage
Ng Seq V low low Lim 0.00...4.00 xUn 1 0.00 Low alarm voltage limit for negative sequence
voltage
Ng Seq V deadband 100...100000 1 10000 Deadband configuration value for negative
sequence voltage for integral calculation.
(percentage of difference between min and
max as 0,001 % s)
Zro V Hi high Lim
0.00...4.00 xUn 1 0.20 High alarm voltage limit for zero sequence
voltage
Zro V High limit 0.00...4.00 xUn 1 0.05 High warning voltage limit for zero sequence
voltage
Zro V low limit 0.00...4.00 xUn 1 0.00 Low warning voltage limit for zero sequence
voltage
Zro V low low Lim 0.00...4.00 xUn 1 0.00 Low alarm voltage limit for zero sequence
voltage
Zro V deadband 100...100000 1 10000 Deadband configuration value for zero
sequence voltage for integral calculation.
(percentage of difference between min and
max as 0,001 % s)
8.1.10.5 Monitored data
Table 835: V1,V2,V0 Monitored data
Name
Type Values (Range) Unit Description
V2-kV FLOAT32 0.00...4.00 xUn Measured negative sequence
voltage
V1-kV FLOAT32 0.00...4.00 xUn Measured positive sequence
voltage
V0-kV FLOAT32 0.00...4.00 xUn Measured zero sequence
voltage
V2_INST FLOAT32 0.00...4.00 xUn Negative sequence voltage
amplitude, instantaneous
value
V2_ANGL
FLOAT32 -180.00...180.00 deg Negative sequence voltage
angle
Table continues on next page
1MAC059074-MB A Section 8
Measurement functions
615 series ANSI 925
Technical Manual