6.3.8 Settings
Table 753: MCS-A Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Pickup value 1.0...100.0 %In 0.1 10.0 Pickup value, percentage of the nominal
current
Alarm delay time 100...300000 ms 10 3000 Alarm delay time
Alarm output mode 1=Non-latched
3=Lockout
3=Lockout Select the operation mode for alarm output
Table 754: MCS-A Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
Measurement mode 2=DFT
3=Peak-to-Peak
2=DFT Selects used measurement mode
Table 755: MCS-B Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Disable / Enable
Pickup value 1.0...100.0 %In 0.1 10.0 Pickup value, percentage of the nominal
current
Alarm delay time 100...300000 ms 10 3000 Alarm delay time
Alarm output mode 1=Non-latched
3=Lockout
3=Lockout Select the operation mode for alarm output
Table 756: MCS-B Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
Measurement mode 2=DFT
3=Peak-to-Peak
2=DFT Selects used measurement mode
1MAC059074-MB A Section 6
Supervision functions
615 series ANSI 859
Technical Manual