Parameter Values (Range) Unit Step Default Description
Value maximum -10000.0...10000.0 1 10000.0 Maximum output value for scaling and
supervision
Value minimum -10000.0...10000.0 1 -10000.0 Minimum output value for scaling and
supervision
Val high high limit -10000.0...10000.0 1 10000.0 Output value high alarm limit for supervision
Value high limit -10000.0...10000.0 1 10000.0 Output value high warning limit for supervision
Value low limit -10000.0...10000.0 1 -10000.0 Output value low warning limit for supervision
Value low low limit -10000.0...10000.0 1 -10000.0 Output value low alarm limit for supervision
Value deadband 100...100000 1 1000 Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
3.13.5 Monitored data
Table 60: Monitored data
Name Type Values (Range) Unit Description
AI_DB1 FLOAT32 -10000.0...10000
.0
mA input, Connectors 1-2,
reported value
AI_RANGE1 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
mA input, Connectors 1-2,
range
AI_DB2 FLOAT32 -10000.0...10000
.0
mA input, Connectors 3-4,
reported value
AI_RANGE2 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
mA input, Connectors 3-4,
range
AI_DB3 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
5-6-11c, reported value
AI_RANGE3 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
5-6-11c, range
AI_DB4 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
7-8-11c, reported value
AI_RANGE4 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
7-8-11c, range
AI_DB5 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
9-10-11c, reported value
Table continues on next page
Section 3 1MAC059074-MB A
Basic functions
128 615 series ANSI
Technical Manual