EasyManua.ls Logo

ABB 615 Series - Technical Data

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.1.11.6 Technical data
Table 841: P, E Technical data
Characteristic
Value
Operation accuracy At all three currents in range 0.10…1.20 × I
n
At all three voltages in range 0.50…1.15 × V
n
At the frequency f
n
±1 Hz
±1.5% for apparent power S
±1.5% for active power P and active energy
1)
±1.5% for reactive power Q and reactive energy
2)
±0.015 for power factor
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1) |PF| >0.5 which equals |cosφ| >0.5
2) |PF| <0.86 which equals |sinφ| >0.5
8.1.11.7 Technical revision history
Table 842: P, E Technical revision history
Technical revision Change
B Demand values added to Monitored data. Recorded
data added to store minimum and maximum demand
values with timestamps.
C
Internal improvement.
D Internal improvement.
8.1.12 Single-phase power and energy measurement SP, SE
8.1.12.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single-phase power and energy
measurement
SPEMMXU SP, SE SP, SE
Section 8 1MAC059074-MB A
Measurement functions
930 615 series ANSI
Technical Manual