EasyManua.ls Logo

ABB 615 Series - Input Linear Scaling; Measurement Chain Supervision

ABB 615 Series
1196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.13.2.3 Input linear scaling
Each RTD/mA input can be scaled linearly by the construction of a linear output function
in respect to the input. The curve consists of two points, where the y-axis (Input minimum
and Input maximum) defines the input range and the x-axis (Value minimum and Value
maximum) is the range of the scaled value of the input.
The input scaling can be bypassed by selecting Value unit = "Ohm" when
Input mode = "Resistance" is used and by selecting Value unit = "Ampere"
when Input mode = "0...20 mA" is used.
Example for linear scaling
Milliampere input is used as tap changer position information. The sensor information is
from 4 mA to 20 mA that is equivalent to the tap changer position from -36 to 36,
respectively.
Input maximum
Input minimum
Input mode
”0..20mA”
4 mA
20 mA
Value minimum
-36
AI_VAL#
Value maximum
36
Value unit
”Dimensionless”
X130-Input#
GUID-85338A5E-3D2F-4031-A598-EA8A525190D3 V1 EN
Figure 30: Milliampere input scaled to tap changer position information
3.13.2.4 Measurement chain supervision
Each input contains a functionality to monitor the input measurement chain. The circuitry
monitors the RTD channels continuously and reports a circuitry break of any enabled
input channel. If the measured input value is outside the limits, minimum/maximum value
is shown in the corresponding output. The quality of the corresponding output is set
accordingly to indicate misbehavior in the RTD/mA input.
Section 3 1MAC059074-MB A
Basic functions
116 615 series ANSI
Technical Manual

Table of Contents

Other manuals for ABB 615 Series

Related product manuals