10.4.7 Settings
Table 940: PQVUB Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Opeartion Enable/Disable
Unb detection method 1=Neg Seq
2=Zero Seq
3=Neg to Pos Seq
4=Zero to Pos Seq
5=Ph vectors Comp
3=Neg to Pos Seq Set the operation mode for voltage unbalance
calculation
Unbalance pickup Val 1...100 % 1 1 Voltage unbalance pickup value
Trigger mode 1=Single
2=Periodic
3=Continuous
3=Continuous Specifies the observation period triggering
mode
Percentile unbalance 1...100 % 1 95 The percent to which percentile value
PCT_UNB_VAL is calculated
Obs period selection 1=1 Hour
2=12 Hours
3=1 Day
4=7 Days
5=User defined
5=User defined Observation period for unbalance calculation
User Def Obs period 1...168 h 1 168 User define observation period for statistic
calculation
Obs period Str year 2008...2076 2011 Calendar time for observation period start year
in YYYY
Obs period Str month 0=reserved
1=January
2=February
3=March
4=April
5=May
6=June
7=July
8=August
9=September
10=October
11=November
12=December
1=January Calendar time for observation period start
month
Obs period Str day 1...31 1 Calendar time for observation period start day
Obs period Str hour 0...23 h 0 Calendar time for observation period start hour
Section 10 1MAC059074-MB A
Power quality measurement functions
1070 615 series ANSI
Technical Manual