6.5.8 Monitored data
Table 773: 60 Monitored data
Name
Type Values (Range) Unit Description
60 Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
6.5.9 Technical data
Table 774: 60 Technical data
Characteristic Value
Trip time
1)
NPS function V
Fault
= 1.1 × set
Neg
Seq voltage Lev
<33 ms
V
Fault
= 5.0 × set
Neg
Seq voltage Lev
<18 ms
Delta function ΔV = 1.1 × set
Voltage
change rate
<30 ms
ΔV = 2.0 × set
Voltage
change rate
<24 ms
1) Includes the delay of the signal output contact, f
n
= 50 Hz, fault voltage with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
6.5.10 Technical revision history
Table 775: 60 Technical revision history
Technical revision
Change
B Internal improvement
C Internal improvement
D Function name changed from SEQRFUF to
SEQSPVC
1MAC059074-MB A Section 6
Supervision functions
615 series ANSI 873