Table 561: 24 Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
1=enable Operation Mode Disable/Enable
Cooling time 5...10000 s 1 600 Time required to cool the machine
Constant delay 100...120000 ms 10 800 Parameter constant delay
Maximum trip time 500000...10000000 ms 10 1000000 Maximum trip time for IDMT curves
Voltage selection 1=phase-to-earth
2=phase-to-phase
3=pos sequence
3=pos sequence Selection of phase / phase-to-phase / pos
sequence voltages
Phase selection 1=A or AB
2=B or BC
3=C or CA
1=A or AB Parameter for phase selection
Leakage React 0.0...50.0 % 0.1 0.0 Leakage reactance of the machine
Voltage Max Cont 80...160 % 1 110 Maximum allowed continuous operating
voltage ratio
Table 562: 24 Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 100 Resetting time of the trip time counter in DT
mode
Minimum trip time 200...60000 ms 10 200 Minimum trip time for IDMT curves
4.5.6.9 Monitored data
Table 563: 24 Monitored data
Name
Type Values (Range) Unit Description
PICKUP_DUR FLOAT32 0.00...100.00 % Ratio of pickup time / trip time
(in %)
T_ENARESTART INT32 0...10000 s Estimated time to reset of
block restart
VOLTPERHZ FLOAT32 0.00...10.00 pu Excitation level, i.e U/f ratio or
Volts/Hertz
24 Enum 1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
1MAC059074-MB A Section 4
Protection functions
615 series ANSI 657
Technical Manual