Table 845: SP,SE Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Direction of reactive
power flow: forward,
reverse
0...999999999
1 0 Preset Initial value for forward active energy
Reverse Wh Initial 0...999999999 1 0 Preset Initial value for reverse active energy
Forward VArh Initial 0...999999999 1 0 Preset Initial value for forward reactive energy
Reverse VArh Initial 0...999999999 1 0 Preset Initial value for reverse reactive energy
8.1.12.5 Monitored data
Table 846: SP,SE Monitored data
Name Type Values (Range) Unit Description
SA-kVA FLOAT32 -999999.9...9999
99.9
kVA Apparent Power, Phase A
SB-kVA FLOAT32 -999999.9...9999
99.9
kVA Apparent Power, Phase B
SC-kVA FLOAT32 -999999.9...9999
99.9
kVA Apparent Power, Phase C
PA-kW FLOAT32 -999999.9...9999
99.9
kW Active Power, Phase A
PB-kW FLOAT32 -999999.9...9999
99.9
kW Active Power, Phase B
PC-kW FLOAT32 -999999.9...9999
99.9
kW Active Power, Phase C
QA-kVAr FLOAT32 -999999.9...9999
99.9
kVAr Reactive Power, Phase A
QB-kVAr FLOAT32 -999999.9...9999
99.9
kVAr Reactive Power, Phase B
QC-kVAr FLOAT32 -999999.9...9999
99.9
kVAr Reactive Power, Phase C
PFA FLOAT32 -1.00...1.00 Average Power factor, Phase
A
PFB FLOAT32 -1.00...1.00 Average Power factor, Phase
B
PFC FLOAT32 -1.00...1.00 Average Power factor, Phase
C
Max demand SL1 FLOAT32 -999999.9...9999
99.9
kVA Maximum demand for phase A
Max demand SL2 FLOAT32 -999999.9...9999
99.9
kVA Maximum demand for phase B
Max demand SL3 FLOAT32 -999999.9...9999
99.9
kVA Maximum demand for phase
C
Table continues on next page
Section 8 1MAC059074-MB A
Measurement functions
932 615 series ANSI
Technical Manual